1–2 · HF Conducted Emissions

High-Frequency Conducted Emissions in Modern Plants

Modern facilities are dominated by fast-switching power electronics. Their steep voltage edges (high dv/dt) produce emission spectra extending into the MHz range.

Conducted emissions inside the facility network

Following Whitepaper v3.0.0: HF conducted emissions (150 kHz – 30 MHz) are injected by switching equipment and spread over the low-impedance DB and SMDB busbars, where they circulate into neighbouring machines. The facility transformer's high impedance at these frequencies keeps most of the noise inside the plant — so the heat appears on the machine side: in cables and windings through the skin effect, and in motor bearings through common-mode current.

Conducted emissions inside the facility network

Utility gridUtility panelNot fittedFacility transformerHigh HF impedance — noise largely stays inside the facilityMDB-1MDB-2MDB-3SMDB1DBSMDB2DBSMDB3DBSMDB4DBSMDB5DBSMDB6DBSMDB7DBSMDB8DBSMDB9DBSMDB10DBM3~Motor (VFD)=~PV inverter~=Rectifier~=SMPS loadM3~Motor (VFD)=~PV inverter~=Rectifier~=SMPS loadM3~Motor (VFD)=~PV inverterPE / earth

01 · Switching equipment injects HF

VFDs, PV inverters, rectifiers and SMPS switch with steep dv/dt edges, injecting differential- and common-mode HF current (150 kHz – 30 MHz) into their supply cables.

Sites without their own transformer can pass part of this noise on to the utility panel and grid — that case is a separate example.

Where the heat appears (relative)

  • Motor windings & bearings
  • Machine cables
  • DB / SMDB busbars
  • MDB feeders
  • Transformer & utility side

Heat generation threshold

Skin effect in machine cables & windings

50 Hz · δ ≈ 9.2 mm
HF · δ 0.012–0.17 mm

The 50 Hz current uses almost the whole copper section (δ ≈ 9.2 mm). The HF current flows only in a thin surface skin (δ ≈ 0.17 mm at 150 kHz, 0.012 mm at 30 MHz), so its AC resistance — and its I²R heat — is far higher.

Skin thickness exaggerated for visibility.

Illustrative animation based on Whitepaper v3.0.0 — relative levels, not measured values.

Emission sources

Variable-frequency drives (VFDs)

PWM carrier frequencies of 2–16 kHz; steep dv/dt edges generate harmonics into the MHz range.

Switch-mode power supplies (SMPS)

Switching from 20 kHz to several hundred kHz, with fast transitions producing broadband emissions.

Solar PV inverters & rectifiers

High-frequency switching stages coupling conducted noise onto the AC network.

Frequency regimes

10 Hz100 Hz1 kHz10 kHz100 kHz1 MHz10 MHz100 MHzLow-order harmonics< 2.5 kHz · IEEE 519Supraharmonics2 – 150 kHz · IEC 61000-2-2 / researchConducted emissions150 kHz – 30 MHz · CISPR 1150/60 HzVFD 2–16 kHzSMPS 20 kHz → 100s kHz
Frequency regimesHzStd.
Low-order harmonics< 2.5 kHzIEEE 519Handled by harmonic filters and PF-correction capacitors
Supraharmonics2 – 150 kHzIEC 61000-2-2 / researchEmerging regulatory range
Conducted emissions150 kHz – 30 MHzCISPR 11Denka® Platinum Plate design band
SCOPE
Scope: Denka® Platinum Plates are a high-frequency filter. They complement, and do not replace, IEEE 519 low-order harmonic filters and capacitor power-factor correction.[1,2]

Quantified impact — peer-reviewed research

AssetDocumented effect of HF distortionSource
Induction motors — total losses+8.7% to +19% total losses; +8.3 °C average winding temperature; ≈41 W extra loss per 1 °C rise in a 37 kW motor[5,6]Aarniovuori et al., IECON 2013; Jiang et al., 2022
Induction motors — iron losses+29% under load, +86% at no load; up to +13 °C[7]Ding & Mi, 2011
Distribution transformersEddy-current losses up to +33%; insulation ageing 22% faster[8]Yaghoobi et al., 2020
MV/LV cablesSupraharmonic losses 1.6–2.4% of fundamental losses (>10–20% of harmonic losses); partial-discharge activity +10%[9,10]Novitskiy et al., 2020; Mariscotti & Mingotti, 2024
Insulation (all assets)Arrhenius principle: insulation life roughly halves for every 10 °C temperature rise[3]IEEE Std 1-2000
Motor bearingsBearings ≈51% of motor failures; HF common-mode current discharging through stray capacitances causes EDM pitting and fluting[4,11,12,13]IEEE Std 493 (Gold Book); Liu, 2014; Erdman et al., 1996; ABB Technical Guide No. 5